Bring IoT devices to KNX
Integrate IoT devices (e.g. Matter) to KNX. Assign group addresses directly to IoT devices and control them from KNX as if they were just your normal KNX device.
Table of contents
🎬 Video tutorial
Follow our video instructions on how to assign group addresses to your Matter devices.
Quick setup
1. Connect your IoT device to 1Home
Before you begin you have to first connect your IoT device to the 1Home Dashboard.
If you haven't done this already, follow our guides:
2. Bridge IoT device KNX
Go under Integrations -> KNX -> Bridge Devices to KNX
and click on Add Device
. In the image below we have previously already added a Matter Button, now let's also add a Hue light.
Select the device that you would like to control from KNX.
Click on expand device to see all the available KNX group objects.
As you can see, there are all the classic KNX group objects available to be linked with group addresses.
See a list of all supported group objects for different device types.
3. Link group addresses
In ETS you can create your group addresses that you will use to link with your IoT device. Below is our example used in this tutorial.
Then you can click the pencil button on the right side of each group object and choose your group address.
Tips:
- Upload ETS file for easier search - When selecting group addresses you can upload your ETS project file (.knxproj) and we will import all your group addresses.
- Assign multiple group addresses - You can assign more than one group address to the same group objects, for example for central control group address that controls all lights.
4. Managing configuration
You can enable/disable each device bridging if needed.
In case you remove the device and want to use another device with the configuration that you have created, once the initial device is deleted an Replace device
option will be shown.
List of supported group objects for your IoT devices
Looking for supported KNX devices?
If instead you want to see which KNX devices can be configured in 1Home, see the support list of KNX devices.
For each device type we provide different group objects:
Light: On/Off
On/Off Set
- Flags: W - DPT: 1.001 - Turns the light on or off.On/Off Status
- Flags: R,T - DPT: 1.001 - On/off status of the light.
Light: Dimming
On/Off Set
- Flags: W - DPT: 1.001 - Turns the light on or off.On/Off Status
- Flags: R,T - DPT: 1.001 - On/off status of the light.Dimming Relative Set
- Flags: W - DPT: 3.007 - Relative dimming of the light.Dimming Absolute Set
- Flags: W - DPT: 5.001 - Absolute dimming of the light in %.Dimming Absolute Status
- Flags: R,T - DPT: 5.001 - Status of the light in %.
Light: Color Temperature
On/Off Set
- Flags: W - DPT: 1.001 - Turns the light on or off.On/Off Status
- Flags: R,T - DPT: 1.001 - On/off status of the light.Dimming Relative Set
- Flags: W - DPT: 3.007 - Relative dimming of the light.Dimming Absolute Set
- Flags: W - DPT: 5.001 - Absolute dimming of the light in %.Dimming Absolute Status
- Flags: R,T - DPT: 5.001 - Status of the light in %.Color Temperature Kelvin Set
- Flags: W - DPT: 7.600 - Sets the color temperature of the light in Kelvin.Color Temperature Kelvin Status
- Flags: R,T - DPT: 7.600 - Current color temperature of the light in Kelvin.
Light: Color
On/Off Set
- Flags: W - DPT: 1.001 - Turns the light on or off.On/Off Status
- Flags: R,T - DPT: 1.001 - On/off status of the light.Dimming Relative Set
- Flags: W - DPT: 3.007 - Relative dimming of the light.Dimming Absolute Set
- Flags: W - DPT: 5.001 - Absolute dimming of the light in %.Dimming Absolute Status
- Flags: R,T - DPT: 5.001 - Status of the light in %.- Choose in parameters between:
- RGB Combined
RGB Set
- Flags: W - DPT: 232.600 - Set the red, green, blue at the same time.RGB Status
- Flags: R,T - DPT: 232.600 - Status of the red, green, blue of the light.
- RGB Separate
Red Set
- Flags: W - DPT: 5.001 - Set the red value of the light.Red Status
- Flags: R,T - DPT: 5.001 - Status of the red value of the light.Green Set
- Flags: W - DPT: 5.001 - Set the green value of the light.Green Status
- Flags: R,T - DPT: 5.001 - Status of the green value of the light.Blue Set
- Flags: W - DPT: 5.001 - Set the blue value of the light.Blue Status
- Flags: R,T - DPT: 5.001 - Status of the blue value of the light.
- RGB Combined
Socket: On/Off
On/Off Set
- Flags: W - DPT: 1.001 - Turns the light on or off.On/Off Status
- Flags: R,T - DPT: 1.001 - On/off status of the light.
Door Lock
Door Lock/Unlock Set
- Flags: W - DPT: 1.009 - Locks or unlocks the door.Door Lock/Unlock Status
- Flags: R,T - DPT: 1.009 - Status if the doors are locked.
Window Covering
Percentage Set
- Flags: W - DPT: 5.001 - Sets covering to a specific percentage.Percentage Status
- Flags: R,T - DPT: 5.001 - Status of the covering position in percentages.Stop/Step
- Flags: W - DPT: 1.001 - Stops the covering or moves the slats slightly.Up/Down Set
- Flags: W - DPT: 1.001 - Moves the covering up or down.- If slats are supported:
Slats Set
- Flags: W - DPT: 5.001 - Sets slats to a specific percentage.Slats Status
- Flags: R,T - DPT: 5.001 - Status of the slats in percentages.
Push Button
Under Parameters
section in the 1Home dashboard, choose between different ways to bridge the IoT button to KNX:
- Toggle
Toggle Set
- Flags: T - DPT: 1.001 - Sends the toggle command to the device.Toggle Status
- Flags: W - DPT: 1.001 - Stores the on/off value of the device.
- One Button Dimming
Toggle Set
- Flags: T - DPT: 1.001 - Sends the toggle command to the device.Toggle Status
- Flags: W - DPT: 1.001 - Stores the on/off value of the deviceDimming Relative Set
- Flags: T - DPT: 3.007 - Dims the light incrementally up or down.
- One Button Shutters
Open/Close Set
- Flags: T - DPT: 1.001 - Moves the covering up or down.Stop
- Flags: T - DPT: 1.001 - Stops the covering or moves the slats slightly.
- Send Values
- Decide for short press and long press (if available) between different options:
- Disabled
- Send DPT 1 (1-bit) value
Send Value
- Flags: T - DPT: 1.001 - Sends a specific 1-bit value to the bus.
- Send DPT 5 (1-byte unsigned) value
Send Value
- Flags: T - DPT: 5.001 - Sends a specific 1-byte unsigned value to the bus.
- Scene Number
Trigger KNX Scene
-Flags: T - DPT: 17.001 - Activates KNX scene with a specified scene number
- Decide for short press and long press (if available) between different options:
Thermostat
Local Temperature Status
- Flags: R,T - DPT: 9.001 - Current temperature in the area.Setpoint Set
- Flags: W - DPT: 9.001 - Set the desired setpoint temperature.Setpoint Status
- Flags: R,T - DPT: 9.001 - Status of the currently desired setpoint temperature.
Sensor: Contact
Open/Close Status
- Flags: R,T - DPT: 1.009 - Status of the contact sensor.
Sensor: Temperature
Temperature Status
- Flags: R,T - DPT: 9.001 - Status of the temperature.
Sensor: Humidity
Humidity Status
- Flags: R,T - DPT: 9.007 - Status of the humidity in percentages.
Sensor: Brightness
Brightness Status
- Flags: R,T - DPT: 9.004 - Status of the brightness in Lux.
Sensor: Occupancy
Presence Status
- Flags: R,T - DPT: 1.018 - Status of the occupancy.